Runtime Installation

If the HMI device is delivered from the factory without Runtime, at first power up HMI shows the “Runtime Loader” screen.

Runtime can be installed:

Install Runtime via Ethernet

To install Runtime via Ethernet follow the "Download to HMI device" procedure.

WARNING: Runtime installation via Ethernet download requires the HMI to have a valid IP address.

The IP address can be assigned in three ways:

Install Runtime via USB Memory

To install Runtime, UpdatePackage or Backup Package via USB device follow this procedure:

1. Create an Update Package from JMobile Studio and copy into an empty USB memory stick

Note: File systems supported are FAT16/32 and Linux Ext2, Ext3 and Ext4.

2. On HMI select [Startup sequence], then [Install]

3. Double click on “mnt” to access this folder

4. Then on “usbmemory”

5. Select “UpdatePackage.zip” and confirm with [Ok]

6. The runtime installation begin

7. At the end press "Done" button

8. Then "Start HMI" button

Runtime Uninstall

System Settings in Default mode allows to uninstall HMI Runtime or change Startup sequence, this mode is available via tap-tap sequence and can be accessed also when HMI is facing a software failure.

See "Enter System Settings via tap-tap procedure "

To uninstall the Runtime from HMI in Default Mode screen select [Startup Sequence]:

From the installed applications view:

  1. Select the Runtime you want to remove
  2. Uninstall the selected Runtime

Runtime uninstall process will be performed:

At the end press "Done" button